FDC PR10 Series Model PR1006 - Paperless Recorders by Future Design Controls. PR1006-0-A-0-0-1-0-00 Other configurations available
The PR1003 provides Custom Graphic Display Views
The 1006 provides three additional analogy inputs and additional relays and descrete iO over the 1003
Configuration model numberPR1006-0-A-0-0-1-0-00
Call for configurations
This is a standard base model. Power Input 90-264VAC 50/60 HZ. The display is 4.3" and offers a host of standard and optional features. These features include easy to use touch screen interface, 100msec sampling rate, monitor external channels (via TCP/IP or serial modbus), normal & high frequency pulse inputs, batch recording, write free-hand messages directly on the display, supports Field calibration, multilevel security, customizable display, Web Server, email, 20-languages, TCP/IP, SD slot, two USB ports and can meet the requirements for CFR21 part 11, Power Input 90-264VAC 50/60 HZ Firmware AI: Analog input offers congurable log interval:100ms, 1, 2, 5, 10, 20, 30 Sec, 1, 2 Min/Dot.
DI: Digital input congurable as normal Logic or high frequency Pulse. AO: Analog Retransmission Output, mA or VDC.
DO: Digital output/relay output can be enabled. Each DO card has 6 relays.
Display: Congurable display speed: 100ms, 1, 2, 5, 10, 20, 30 Sec/Dot, or 1, 2, 10, 30 Min/Page, 1, 2, 4, 8, 12 Hour/Page, or 1 Day/Page.
Clock: Congurable Date Style (MM/dd/yy or dd/MM/yy), Daylight Savings as well as Time Synchronize via LAN.
Communication: As standard Web Server and email functions are available via LAN.
Instrument: Adjustable display brightness, Screen Saver time as well as other settings.
Security: The Normal Security supports one password. With the optional CFR21 High Security system supports up to 30-users, 9 security levels, password aging, operator audit trail and auto logout.
Demo: Enable or disable the demonstration mode. Printer Auto-output: An automatic output of Historical data, Report data or other preselected data may be sent to a selected printer.System information: Provides Firmware version number, Internal & External memory status, IP address and IO card status of each Slot. Field Calibration: Analog channels may be easily eld calibrated.