DMV-DLE 702/602, Double Solenoid Valve, 24 V, 65 VA, by Dungs 228224
$1,072.93
Item Code: 228224
DMV-DLE 702/602 (228224)
- 1”, 1-1/4”, 1-1/2”, 2” NPT or Rp
24 Vac (+10%/-15%) 50-60 Hz, 65 VA
NEMA Type 12
Replacement Coil: 238825
Replacement PBW: 238806
Formerly: 228-224
Description
The DUNGS Dual Modular Valve (DMV-D(LE)/602) combines two normally closed, automatic
shutoff valves in one compact housing, which can be wired independently or in parallel. Valve
1 (V1) of the DMV-D and DMV-DLE series is fast opening and fast closing. Valve 2 (V2) of the
DMV-D is fast opening, while V2 of the DMV-DLE is slow-opening for smoother light-off. Max.
flow adjustment on V2 provides variable main flow on both models.
Application
The DMV/6 is recommended for industrial and commercial heating applications that require
two safety shutoff valves in series. The DMV is suitable for natural gas, propane, butane, air
and other inert gases.
Optional Approvals
When ordered and installed with Burkert connector plug (part number 253731), the UL
Recognized DMV valve may replace a UL Listed valve. Such a substitution is typically
required for equipment UL Listed to UL 295/UL 795.
Specifications
Body Sizes Pipe Size/ Thread
DMV-D(LE) 701/602 ½” – 1” NPT or Rp
DMV-D(LE) 702/602 1” – 2” NPT or Rp
DMV-D(LE) 703/602 1” – 2” NPT or Rp
Max. Operating Pressure
7 PSI (500 mbar) UF, FM
5 PSI (360 mbar) CSA
Electrical Ratings (+10% / -15%)
110 - 120 Vac / 50-60 Hz
24 Vac/50 – 60 Hz; 24 VDC
Enclosure Rating
NEMA Type 12
Electrical Connection
DIN-connector with ¾” NPT conduit adapter
Operating Time
100% Duty Cycle
Ambient Temperature Rating
-40 F to +150 F (-40 C to +65 C)
Aluminum body; Inlet, intermediate and outlet side taps (G1/8 ISO 228); Inlet gas strainer installed in the housing upstream valves (23 mesh screen); DMV-D - V1 fast opening & closing (<1 s), V2 fast opening & closing (<1 s); DMV-DLE - V1 fast opening & closing (<1s); V2 slow opening 20s MAX @ 70F & fast closing (<1 s); V2 on both models feature a manually adjustable flow rate (<10-100%); 100% duty cycle; Refer to Flow Curves for Body Selection. Conduit Adapter (240671), DIN connector (210319), and flanges must be ordered and priced separately. Code requirements vary. FM requires visual indication on 1" and larger safety valves. Two visual indicators, (VI) 266949 or one CPI 400 (CPI) 266968, and one VI meet this requirement. These also must be ordered separately.