DMV-DLE 702/604L, Double Solenoid Valve with VLA, 120 V, 60 VA, by Dungs 267047
$1,387.58
Item Code: 267047
DMV-DLE 702/604L With VLA (267047)
- 1”, 1-1/4”, 1-1/2”, 2” NPT or Rp
120 Vac (+10%/-15%) 50-60 Hz, 60 VA
NEMA Type 4x
Replacement Coil: 246515
(Valve Requires 2 Coils, Sold Individually)
Formerly: 240-805V
Description
The DUNGS Dual Modular Valve (DMV-D(LE)/604) with a Vent Line Adapter (VLA) that is
factory installed.
For main gas lines:
• Up to 1 1/2”; vent line must be 3/4”
• 2”; vent line must be 1”
Application
The DUNGS DMV-D(LE)/604 is recommended for industrial and commercial heating
applications that require two safety shutoff valves in series with a vent line connection
between the safety shutoff valves and NEMA Type 4x enclosure. The DMV-D(LE)/604 is
suitable for natural gas, propane, butane, air and other inert gases.
Specifications
Body Size Pipe Size/ Thread Vent Line Connection
DMV 702/604 1” – 2” NPT or Rp 1” NPT
DMV 703/604 1” – 2” NPT or Rp 1” NPT
Max Operating Pressure
7 PSI (500 mbar) UL, FM
5 PSI (360 mbar) CSA
Electrical Ratings (+10%/-15)
110 – 120 Vac/ 50-60 Hz
24 Vac 50-60 Hz
24 VDC
Enclosure Rating
NEMA Type 4x
Electrical Connection
Screw terminals with ½” NPT conduit connection
Operating Time
100% Duty Cycle
Ambient Temperature Rating
-20 F to +140 F (-30 C to +60 C)
Aluminum body; Inlet, intermediate and outlet side taps (G1/8 ISO 228); Inlet gas strainer installed in the housing upstream valves (23 mesh screen); DMV-D - V1 fast opening & closing (<1 s), V2 fast opening & closing (<1 s); DMV-DLE - V1 fast opening & closing (<1s); V2 slow opening 20s MAX @ 70F & fast closing (<1 s); V2 on both models feature a manually adjustable flow rate (<10-100%); 100% duty cycle; Refer to Flow Curves for Body Selection. Flanges must be ordered and priced separately. Code requirements vary. FM requires visual indication on 1" and larger safety valves. Two visual indicators, (VI) 266949 or one CPI 400 (CPI) 266968, and one VI meet this requirement. These also must be ordered separately.