Direct Replacement for Eclipse Veriflame

Parameter Specification
Supply Series 5602/5605: 120 VAC (+10%, -15%), 50/60 Hz standard
Series 5603: 240 VAC (+10%, -15%), 50/60 Hz standard
Internal power consumption: 12 VA (excluding external connected loads)
Temperature Ranges
Unit Model Number
Temperature
Veri-Flame All Models
-40 to 140°F (-40 to 60°C)
90 UV Scanner 5600-90A
0 to 140°F (-20 to 60°C)
NEMA4 UV Scanner 5600-91
0 to 257°F (-20 to 125°C)
Self-Check UV 5602-91
0 to 140°F (-20 to 60°C)
Remote Display 5602DBP
32 to 122°F (0 to 50°C)
Flame Failure Response
3 seconds +/- 0.5 seconds
Trial for Ignition (TFI) No Purge & Purge Models:
Series 5602 and 5603: 5 or 10 seconds selectable.
Series 5605: 10 or 15 seconds selectable.
Modulating Model: 5 or 10 seconds selectable.
Pilot Interrupt (if selected)
10 seconds
Purge Time
Selectable from 0 - 255 seconds in 15 second increments
Output ratings for 120 VAC
(maximum total connected load not to exceed 15 amps)*
Function
Terminals
UL Inductive Load
Relay Contact Rating Resistive Load
Gas Valve
3, 5
175 VA, 1/10 HP
10 amps
Ignition
4
375 VA
10 amps
Motor or Contactor
8
470 VA, 1/2 HP
16 amps
Control Signal
A, 10, 11, 12, 13
175 VA
10 amps
Output ratings for 240 VAC
(maximum total connected load notto exceed 15 amps)*
Function
Terminals
Relay Contact Rating Resistive Load
Valves, Ignition
3, 4, 5
5 amps
Motors or Contactor
8
16 amps
Alarm
A
5 amps
Controls
10, 11, 12, 13
5 amps
Approvals • No Purge and Purge Models:
Series 5602: UL listed for the USA and Canada; FM approved
Series 5603: FM approved
Series 5605: UL listed; FM approved

• Modulating Models:
Series 5602: UL recognized for US and Canada, must be mounted in panel;
FM approved
Series 5603: FM approved
Shipping Weight • 1.4 kilograms (3.1 lbs) for all models
• 0.5 kilograms (1.1 lb) for Models 5602-10P & 5602-10-1P bases
• 1.2 kilograms (2.7 lbs) for Model 5602-40 base
*Resistive loads have inrush currents approximately the same as steady state operation. The inductive inrush current must be less than 10 times the rating. The inrush current must not be applied more than once every 15 seconds.