120 GPH / 240 Kg/Hr / 10.9 Mmbtu/hr

Algas-SDI Direct Fired 120/60H LP Gas

Ideal for applications that lack electricity or requires portability

Specifications
Vaporization Type Direct Fired / Flow Through
Electrical Data None Required
Model Number 120/60H
Design Pressure 290 PSI / 20.0 Barg
Relief Valve Set Point 250 PSIG / 17.2 Barg
Hydrostatic Pressure 435 PSIG / 29.9 Barg
Vaporizer Approvals: ASME, UL (US and Canada)
CE, PED (DNV)
Liquid Inlet (FNPT) 3/4"
Liquid Outlet (FNPT) 1"
Vaporization Capacity 240 Kg/h
120 US Gal/h
10.9 MMBTU/h
Burner Input 38.8 Kcal/h
154.1 BTU/h
Burner Ignition 9vdc Re-igniter standard on all units
Shipping Weight 275 lbs
125 kg
Shipping Dimensions Length 21"
Width 35"
Height 52"

Key Points
  • No electricity required
  • Auto re-ignitor standard
  • Double liquid carry-over protection
  • Thermostat easily operated with gloves
  • Easy access inlet valve
  • Low profile (40/40 thru 120/60) for ease of portability
  • Proprietary capacity control valve prevents lock up
  • Burner gas isolation valve provided
  • Thermowell allows easy replacement of gas valve
  • “Snap-in” 40/40 pilot assembly

Operational Overview

By design, DF series direct fired vaporizers apply heat directly to a pressure vessel containing liquid LPG. The heating process induces vaporization, while consuming a small amount of the vapor generated. DF series vaporizers ensure a continuous vapor supply to your application.


Algas-SDI vaporizers are build tough. A rugged heavy gauge metal enclosure with power coat applied over zinc plating protects against harsh environments. The stainless-steel exhaust flue and stainless-steel tubing eliminates potential clogging of the vaporizer’s temperature controller and burner orifices.


Access to the vaporizer internals is provided via A latch-less reliable door panel. The design allows easy removal of the burner if required. Our domed exhaust top combined with our unique flue collar design, prevents water rain infiltration to the burner. Algas-SDI Provides an automatic 9VDC re-ignitor as standard. When service requires replacement of the re-igniter, spade connectors make the field change simple. Removal of the 9VDC battery allows the end user to disable the re-ignitor.