DMV-D 704/604, Double Solenoid Valve, 120 V, 110 VA, by Dungs (Formerly 241625)
$0.00
Item Code: 293818
DMV-D 704/604 (241625)
- 2” NPT or Rp
120 Vac (+10%/-15%) 50-60 Hz, 110 VA
NEMA Type 4x
CSA Approved ONLY
Replacement Coil: 246517
(Valve Requires 2 Coils, Sold Individually)
Formerly: 241-625
Description
The DUNGS Dual Modular Valve (DMV-D(LE)/604) combines two normally closed, automatic
shutoff valves in one compact housing (Rated as a NEMA Type 4x enclosure), which can be
wired independently or in parallel. Valve 1 (V1) of the DMV-D and DMV-DLE series is fast
opening and fast closing. Valve 2 (V2) of the DMV-D is fast opening, while V2 of the DMVDLE
is slow-opening for smoother light-off. Max. flow adjustment on V2 provides variable
main flow on both models.
Application
The DUNGS DMV-D(LE)/604 is recommended for industrial and commercial heating
applications that require two safety shutoff valves in series with a NEMA Type 4x enclosure.
The (DMV-D(LE)/604) is suitable for natural gas, propane, butane, air and other inert gases.
Specifications
Body Size Pipe Size/ Thread
DMV-D(LE) 702/604 1” – 2” NPT or Rp
DMV-D(LE) 703/604 1” – 2” NPT or Rp
DMV-D(LE) 704/604 2” NPT or Rp
Max Operating Pressure
7 PSI (500 mbar) UL, FM
5 PSI (360 mbar) CSA
Max. Close Off Pressure
10 PSI (700 mbar) UL, FM
Electrical Ratings (+10%/-15)
110 – 120 Vac/ 50-60 Hz
Enclosure Rating
NEMA Type 4x
Electrical Connection
Screw terminals with ½” NPT conduit connection
Operating Time
100% Duty Cycle
Ambient Temperature Rating
-20 F to +140 F (-30 C to +60 C)
(704) +5 F to +140 F (-15 C to +60 C)
Aluminum body; Inlet, intermediate and outlet side taps (G1/8 ISO 228); Inlet gas strainer installed in the housing upstream valves (23 mesh screen); DMV-D - V1 fast opening & closing (<1 s), V2 fast opening & closing (<1 s); DMV-DLE - V1 fast opening & closing (<1s); V2 slow opening 20s MAX @ 70F & fast closing (<1 s); V2 on both models feature a manually adjustable flow rate (<10-100%); 100% duty cycle; Refer to Flow Curves for Body Selection. Flanges must be ordered and priced separately. Code requirements vary. FM requires visual indication on 1" and larger safety valves. Two visual indicators, (VI) 266949 or one CPI 400 (CPI) 266968, and one VI meet this requirement. These also must be ordered separately.